Plan Review Notes For Permit 01061269 |
Permit Number |
01061269 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-07-03 00:00:00 | FAILED... | | | | 1) DEMO PERMITS REQUIRED | | | | 2) COVER SHEET SHOWS PLUMBING PAGES P-1, | | P-2, AND P-3. NO P-3 SHEET FOUND. PLEASE | | UBMIT FULL SET OF PLANS. | | | | 3) DRY HORIZONTAL VENT SHOWN AFTER BIDET | | IN BATH #1 NOT ALLOWED PER SPC-94 SECT. | | 906.2 | | | | 4) DRY HORIZONTAL VENT SHOWN AFTER | | SHOWER IN BATH #2 NOT ALLOWED PER SPC-94 | | SECT. 906.2 | | | | 5) DRY HORIZONTAL VENT SHOWN AFTERSHR | | IN BATH #3 NOT ALLOWED PER SPC-94 SECT. | | 906.2 | | | | 6) CLEAN OUT REQUIRED ON WASH MACHINE | | STACK AT 4' ABOVE FLOOR. | | | | 7) PAN DRAIN FOR WATER HEATER EMERGENCY | | PAN TO BE 1". | | | | 8) 3" VENT THROUGH ROOF REQUIRED PER SPC | | -94 SECT. 904.3.1. NONE SHOWN ON SANT. | | RISER DIAGRAM. | | | | 9) SEPARATE GAS PERMIT REQUIRED. SEE | | ATTACHED GAS PERMIT APPLICATION REQUIRE- | | MENTS SHEET FOR REQUIRED INFORMATION. | | | | 10) BACKFLOW REQUIRED FOR POOL | | | | 11) SEPARATE PERMIT FOR IRRIGATION. | | PLUMBING CONTRACTOR CUT INTO WATER | | SERVICE AND LEAVE A VALVE AND AN ADAPTOR | | FOR IRRIGATION IF NONE IS AVAILABLE. | | | | 12) SANITARY RISER DIAGRAM SHOWS A LAV | | NEXT TO THE DISHWASHER. PLEASE CLARIFY | | IF THAT IS A LAV OR KIT. SINK. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT. 8377 |
|