2001-08-07 00:00:00 | *************BUILDING UNSAT************* |
| |
| 1)IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY, PLANS STAMPED BY THEM AND |
| COPY OF RECEIPT SUBMITTED TO CITY OF |
| WEST PALM BEACH BUILDING DEPARTMENT, |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| |
| 2) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 3) PROVIDE ATTIC ACCESS AND ATTIC |
| VENTILATION PER 97 SBC 2309.6 AND 2309.7 |
| |
| 4) PROVIDE FOUNDATION VENTILATION PER |
| 97 SBC 1804.6.2.1. |
| |
| 5) PROVIDE DESIGN CERTIFICATION FOR |
| BUILDING CODE COMPLIANCE FORM, COMPLETED |
| SIGNED, SEALED AND DATED BY THE DESIGNER |
| OF RECORD. AMENDMENTS 104.2.2 |
| |
| 6) INDICATE ROOF PITCH AND MEAN ROOF |
| HEIGHT ON PLANS. |
| |
| 7) INDICATE SPECIAL ROOF SHEATHING |
| NAILING ZONES. AMENDMENTS 2306 |
| |
| 8) PROVIDE ROOF FRAMING PLAN INDICATING |
| CONNECTORS TO BE USED AND UPLIFT TO BE |
| RESISTED. THE SIMPSON H1 CONNECTOR |
| INDICATED ON THE PLANS IS NOT SUFFICIENT |
| TO ANCHOR GIRDER TRUSS H6. |
| |
| 9) PROVIDE CLEAR SETS OF PLANS. IT IS |
| DIFFICULT TO READ AND SEE DETAILS ON THE |
| PLANS WITH ALL THE ADDITIONAL MARKING |
| AND WRITING OVER THE DRAWINGS. CITY |
| AMENDMENTS 104.2.1 |
| |
| 10) THE ADDITION DOES NOT COMPLY WITH |
| TABLE 600 OF THE 97 SBC. THE PERCENT OF |
| OPENINGS ALLOWED FOR A DISTANCE OF OVER |
| 3'TO 10'FROM THE PROPERTY LINE IS 20% |
| OF THE WALL AREA (FROM FLOOR TO CEILING) |
| |
| 11) PROVIDE THE DISTANCE BETWEEN THE |
| ADDITION AND EXISTING COTTAGE. INDICATE |
| THE NUMBERS AND SIZES OF ALL GLAZED |
| OPENINGS IN WALL OF COTTAGE FACING |
| ADDITION SO THAT TABLE 600 ALLOWED |
| OPENING AREAS CAN BE CALCULATED. |
| |
| 12)PROVIDE ENERGY CALCULATIONS AND |
| EQUIPMENT SIZING CALCULATIONS (MANUAL J) |
| AS REQUIRED BY THE 1997 FLORIDA ENERGY |
| EFFICIENCY CODE FOR BUILDING |
| CONSTRUCTION. |
| |
| 13) INDICATE ON PLANS THAT SUITABLE |
| BLOCKING OR BACKING WILL BE PROVIDED FOR |
| THE INSTALLATION OF STORM PANELS. |
| |
| 14) PROVIDE (2) COPIES OF INSTALLATION |
| SCHEDULES AND KEY PLANS FOR STORM PANELS |
| INDICATE THE SPECIFIC TYPES OF ANCHORS |
| AND MOUNTING OPTION THAT IS TO BE USED. |
| |
| 15) PROVIDE (2) CURRENT AND COMPLETE |
| COPIES OF SBCCI OR METRO-DADE PRODUCT |
| APPROVALS FOR: |
| - STRUCTURAL WINDOW MULLIONS |
| - SKYLITES IF BEING INSTALLED |
| |
| 16) PROVIDE DETAILS FOR DECK AND STAIR |
| GUARDRAILS ( HEIGHT, SPACE BETWEEN |
| INTERMEDIATE RAILS, ETC.). 97 SBC 1015 |
| |
| 17) THE PROJECT DESCRIPTION ON THE |
| PERMIT APPLICATION INDICATES A NEW ROOM |
| OVER EXISTING LAUNDRY ROOM. SHOULD THIS |
| STATE NEW ROOF? PLEASE CLARIFY. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)659-8096 EXT.8202 |
| |
| TRUSSES |
| UNSAT |
| |
| 1) THE TRUSS LAYOUT IS REQUIRED TO BE |
| WET SIGNED, SEALED AND DATED BY THE |
| TRUSS ENGINEER. |
| |
| 2) THE TRUSS LAYOUT MUST BE REVIEWED AND |
| APPROVED BY THE DESIGNER OF THE |
| STRUCTURE AND SIGNED BY HIM OR HER. |
| |
| 3) ALL OF THE TRUSS DRAWINGS ARE |
| REQUIRED TO BE SIGNED, SEALED AND DATED |
| BY THE TRUSS ENGINEER. |