Date |
Text |
2001-08-07 00:00:00 | ************** UNSAT ******************* |
| |
| 1)NOTE: PLEASE NOTE THAT PERMIT |
| APPLICATION DOES NOT CORRELATE WITH |
| PLANS SUBMITTED FOR REVIEW. PERMIT APP |
| SAY NEW FLA |
| ROOM AND SECOND FLOOR ADDITION ON HOUSE. |
| YET PLANS SHOW COTTAGE. WHICH ONE? |
| |
| |
| 2)NOTE: PLEASE NOTE PLANS SHOW NEW |
| SERVICE BEING INSTALLED. PLEASE CLARFIY |
| HOW |
| MAIN HOUSE IS BEING FED? |
| GROUNDING ELECTRODE SYSTEM PER 250-50 |
| WIRE SIZES, |
| CONDUIT SIZES, |
| AIC RATINGS, |
| ETC |
| |
| NOT ENOUGH ELECTRICAL DETAIL WAS |
| SUBMITTED FOR FULL REVIEW OF PLANS. |
| PLEASE ALSO HAVE PLANS REDRAWN FOR |
| ELECTRICAL, THERE ARE WAY TOO MANY |
| HANDWRITTEN CHANGES FOR FIRST TIME IN. |
| PER COUNTY-WIDE AND CITY-WIDE |
| ADMINISTRATIVE CODE.104.2 |
| |
| |
| 4)NOTE: SMOKE DETECTORS ARE REQUIRED |
| INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| ALSO ON EACH LEVEL OF A MULTI-LEVEL |
| DWELLING UNIT. ROOMS WITH BATHS AND OR |
| CLOSETS ARE CONSIDERED SLEEPING ROOMS. |
| PER NFPA-72 2-2.1.1.1. |
| |
| 5) NOTE: PLEASE LIST THE REQ`D BATH(S) |
| CIRCUIT(S) PER 210-11-C-3. |
| MUST BE 20A AND #12AWG. |
| |
| 6) PLEASE NOTE MISSING OUTLET FOR A/C |
| EQUIPMENT PER 210-63 OF NEC AND 309.1 |
| MECHANICAL CODE. |
| |
| PLEASE SUBMIT ALL THE ABOVE INFORMATION |
| FOR REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-659-8096 EXT 8372 |