Plan Review Notes
Plan Review Notes For Permit 01061260
Permit Number 01061260
Review Stop E
Sequence Number 1
Notes
Date Text
2001-08-07 00:00:00************** UNSAT *******************
  
 1)NOTE: PLEASE NOTE THAT PERMIT
 APPLICATION DOES NOT CORRELATE WITH
 PLANS SUBMITTED FOR REVIEW. PERMIT APP
 SAY NEW FLA
 ROOM AND SECOND FLOOR ADDITION ON HOUSE.
 YET PLANS SHOW COTTAGE. WHICH ONE?
  
  
 2)NOTE: PLEASE NOTE PLANS SHOW NEW
 SERVICE BEING INSTALLED. PLEASE CLARFIY
 HOW
 MAIN HOUSE IS BEING FED?
 GROUNDING ELECTRODE SYSTEM PER 250-50
 WIRE SIZES,
 CONDUIT SIZES,
 AIC RATINGS,
 ETC
  
 NOT ENOUGH ELECTRICAL DETAIL WAS
 SUBMITTED FOR FULL REVIEW OF PLANS.
 PLEASE ALSO HAVE PLANS REDRAWN FOR
 ELECTRICAL, THERE ARE WAY TOO MANY
 HANDWRITTEN CHANGES FOR FIRST TIME IN.
 PER COUNTY-WIDE AND CITY-WIDE
 ADMINISTRATIVE CODE.104.2
  
  
 4)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
  
 5) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 6) PLEASE NOTE MISSING OUTLET FOR A/C
 EQUIPMENT PER 210-63 OF NEC AND 309.1
 MECHANICAL CODE.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372