Plan Review Notes
Plan Review Notes For Permit 01061193
Permit Number 01061193
Review Stop M
Sequence Number 1
Notes
Date Text
2001-07-17 00:00:00******************PROVISO***************
  
  
  
 FAN SHUTDOWN BY DUCT SMOKE DETECTOR WITH
 NOTIFICATION TO ALARM/STROBE IN
 NORMALLY OCCUPIED AREAS (1997 SMC 406.1
 & NFPA90A 4-4.4.3).