Plan Review Notes For Permit 01061193 |
Permit Number |
01061193 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-07-02 00:00:00 | ****************** UNSAT ************* | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW EQUIPMENT BEING INSTALLED. | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | 2)NOTE: PLEASE NOTE THAT PLANS ARE SHOW- | | ING AN ELECTRICAL ROOM WITH TWO PANELS. | | PLEASE CLARIFY LOCATION OF PANELS FOR | | TWO DIFFERENTTENANTS. PLEASE NOTE THAT | | PANEL "A" CIRCUITS AND PANEL CAN N0T BE | | IN SAME TENANT SPACE AS PANEL "D". | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE NAY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|