Plan Review Notes
Plan Review Notes For Permit 01061068
Permit Number 01061068
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-06-28 00:00:001) THE FIRE DEPARTMENT CONNECTION SHOWN
 ON PAGE C-12 FACES THE WRONG DIRECTION.
 THE CONNECTION SHOULD FACE THE SERVICE
 ROAD AND NOT THE CMU WALL.
 2) A PLATEAU AREA FOR OUTDOOR EXHIBITS
 IS NOTED ON THE PLANS. WRITER QUESTIONED
 MIKE ROSSIN AND HE EXPLAINED THAT ONLY
 TENTS THAT HAVE BEEN PROPERLY PERMITTED
 AND APPROVED BY THE CITY WILL BE USED
 IN THIS AREA.
 3) FLORIDA AVENUE STILL NEEDS ADDITIONAL
 FIRE HYDRANTS.
 4) THIS REVIEW DOES NOT INCLUDE FIRE
 HYDRANT LOCATIONS FOR ALABAMA AVENUE,
 "L" STREET, "N" STREET, ETC.
 5) CITY CODE SECTION 11-4, REQUIRES 18
 FEET FROM OBSTRUCTIONS TO FIRE HYDRANTS.
 6) PLEASE PROVIDE THIS OFFICE A LETTER
 INDICATING THAT ADDITIONAL FIRE HYDRANTS
 WILL BE PROVIDED FOR THE CONVENTION
 CENTER. LOCATION OF THESE HYDRANTS WILL
 BE DETERMINED IN THE NEAR FUTURE.
 7) GAS INSTALLATIONS TO COMPLY WITH
 NFPA 54.
 8) ANY CHANGES IN ELEVATIONS OUTSIDE
 THE CENTER THAT COMPRISE TWO STEPS MUST
 HAVE TREADS OF AT LEAST 13" WIDE AND BE
 VISIBLE TO THE USERS.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910