Plan Review Notes For Permit 01061068 |
Permit Number |
01061068 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-06-28 00:00:00 | 1) THE FIRE DEPARTMENT CONNECTION SHOWN | | ON PAGE C-12 FACES THE WRONG DIRECTION. | | THE CONNECTION SHOULD FACE THE SERVICE | | ROAD AND NOT THE CMU WALL. | | 2) A PLATEAU AREA FOR OUTDOOR EXHIBITS | | IS NOTED ON THE PLANS. WRITER QUESTIONED | | MIKE ROSSIN AND HE EXPLAINED THAT ONLY | | TENTS THAT HAVE BEEN PROPERLY PERMITTED | | AND APPROVED BY THE CITY WILL BE USED | | IN THIS AREA. | | 3) FLORIDA AVENUE STILL NEEDS ADDITIONAL | | FIRE HYDRANTS. | | 4) THIS REVIEW DOES NOT INCLUDE FIRE | | HYDRANT LOCATIONS FOR ALABAMA AVENUE, | | "L" STREET, "N" STREET, ETC. | | 5) CITY CODE SECTION 11-4, REQUIRES 18 | | FEET FROM OBSTRUCTIONS TO FIRE HYDRANTS. | | 6) PLEASE PROVIDE THIS OFFICE A LETTER | | INDICATING THAT ADDITIONAL FIRE HYDRANTS | | WILL BE PROVIDED FOR THE CONVENTION | | CENTER. LOCATION OF THESE HYDRANTS WILL | | BE DETERMINED IN THE NEAR FUTURE. | | 7) GAS INSTALLATIONS TO COMPLY WITH | | NFPA 54. | | 8) ANY CHANGES IN ELEVATIONS OUTSIDE | | THE CENTER THAT COMPRISE TWO STEPS MUST | | HAVE TREADS OF AT LEAST 13" WIDE AND BE | | VISIBLE TO THE USERS. | | | | CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|