2001-06-24 00:00:00****************** UNSAT **************
  
 1)NOTE: PLEASE NOTE THAT UNDER F.A.C
 AND F.S. 61G15-23.002 ALL PLANS THAT
 ARE DONE BY AN ENGINEER ARE TO HAVE
 TITLE BLOCKS CONTAINING ALL THE INFORMAT
 ON ENG OF RECORD.
 ALL MUST BE SIGNED, DATED AND SEALED.
 SIGNATURE AND DATE MUST BE ORIG WET SIG.
  
  
 2)NOTE: PLEASE NOTE THAT LOAD CALCULATIO
 NS NEED TO BE SUBMITTED WITH ALL NEW
 LOAD S ADDED TO EXISTING ELETCRICAL
 SERVICE. PLEASE ALSO SHOW SIZEAND LOAD
 ON EXIT SERVICE.215-5
  
 3)NOTE: PLEASE NOTE THAT FEED TO0 NEW
 PANEL SHOWS 3-#6`S AND NO EQUIPMENT
 GROUNDING CONDUCTOR. PLEASE CLARIFY
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  