Plan Review Notes For Permit 01061037 |
Permit Number |
01061037 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-06-24 00:00:00 | ****************** UNSAT ************** | | | | 1)NOTE: PLEASE NOTE THAT UNDER F.A.C | | AND F.S. 61G15-23.002 ALL PLANS THAT | | ARE DONE BY AN ENGINEER ARE TO HAVE | | TITLE BLOCKS CONTAINING ALL THE INFORMAT | | ON ENG OF RECORD. | | ALL MUST BE SIGNED, DATED AND SEALED. | | SIGNATURE AND DATE MUST BE ORIG WET SIG. | | | | | | 2)NOTE: PLEASE NOTE THAT LOAD CALCULATIO | | NS NEED TO BE SUBMITTED WITH ALL NEW | | LOAD S ADDED TO EXISTING ELETCRICAL | | SERVICE. PLEASE ALSO SHOW SIZEAND LOAD | | ON EXIT SERVICE.215-5 | | | | 3)NOTE: PLEASE NOTE THAT FEED TO0 NEW | | PANEL SHOWS 3-#6`S AND NO EQUIPMENT | | GROUNDING CONDUCTOR. PLEASE CLARIFY | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|