Plan Review Notes
Plan Review Notes For Permit 01061018
Permit Number 01061018
Review Stop P
Sequence Number 1
Notes
Date Text
2001-06-25 00:00:00FAILED..
  
 1) PLEASE SUBMIT POOL HEATER SPEC SHEET.
  
 2) PLEASE SUBMIT INFO ON HOW THE SPRAY
 BARS ARE GOING TO BE PIPED AT THE POOL
 EQUIPMENT. ALSO SUBMIT SPEC SHEET ON
 SPRAY BAR ASSEMBLY.
  
 3) SPA MAIN DRAIN NOT SHOWN ON PIPING
 DIAGRAM AT EQUIPMENT.
  
 4) ONE SKIMMER SHOWN ON PIPING DIAGRAM
 AT POOL EQUIPMENT, TWO ARE SHOWN AT POOL
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377