Plan Review Notes For Permit 01061005 |
Permit Number |
01061005 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-06-24 00:00:00 | ******* UNSAT ****** | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW EQUIPMENT BEING INSTALLED. | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | PLEASE SEE LETTER ATTACHED AND SUBMIT TH | | E ABOVE INFORMATION FOR REVIEW. IF THERE | | ARE ANY QUESTIONS, PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|