2001-08-31 00:00:00************BUILDING PROVISO************
  
 1)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - GARAGE DOORS (PRIOR TO INSTALLATION)
  
 2) STRUCTURE IS LOCATED IN AN AO FLOOD
 ZONE AN ELEVATION CERTIFICATE IS
 REQUIRED.
  
 3) IF OPTIONS ARE USED, THE CORRESPOND-
 ING PRODUCT APPROVALS MUST BE SUBMITTED.
 MANUFACTURER'S SPECIFICATIONS AND LIST-
 ING INFORMATION IS REQUIRED IF OPTIONAL
 BBQ IS INSTALLED.
  
 4) PROVIDE PRODUCT APPROVALS, KEY PLAN
 AND INSTALLATION SCHEDULE FOR STORM
 PANELS UNDER A SEPARATE PERMIT.
  
  
 TRUSSES
 UNSAT
  
 1) THE TRUSS ENGINEERS TITLE BLOCK (NAME
 ADDRESS AND NUMBER) IS REQUIRED ON THE
 TRUSS LAYOUT.
  
 2) THE TRUSS DRAWINGS REFERENCE
 INCORRECT DESIGN CRITERIA (ASCE 7-93),
 THE PROPER CRITERIA IS ASCE 7-95 WITH
 (145 MPH WINDLOAD) OR 1997 SBC SECTION
 1606 WITH (110 MPH WINDLOAD). PLEASE
 CORRECT.
  
 3) THE TRUSS DETAILS FOR BRACING, GABLES
 OVERHANG, PIGGYBACKS, ETC.
  
 4) TRUSS DRAWINGS TG33, T34 AND T35 ARE
 NOT SHOWN ON THE TRUSS LAYOUT AND THERE
 ARE NO TRUSS DRAWINGS FOR TRUSSES TG31,
 T32 AND T33 WHICH ARE INDICATED ON THE
 TRUSS LAYOUT. PLEASE CORRECT.
  
 5) THERE ARE TWO TRUSS DRAWINGS FOR THE
 SAME TRUSS WITH DIFFERENT UPLIFT VALUES
 LISTED. PLESAE CORRECT.
  
 NOTE:
 THESE COMMENTS APPLY TO THE FOLLOWING
 PERMIT NUMBERS: 01060846, 01060847,
 01060848, 01060849.