2001-08-31 00:00:00 | ************BUILDING PROVISO************ |
| |
| 1)PROVIDE (2) CURRENT AND COMPLETE |
| COPIES OF SBCCI OR METRO-DADE PRODUCT |
| APPROVALS FOR: |
| - GARAGE DOORS (PRIOR TO INSTALLATION) |
| |
| 2) STRUCTURE IS LOCATED IN AN AO FLOOD |
| ZONE AN ELEVATION CERTIFICATE IS |
| REQUIRED. |
| |
| 3) IF OPTIONS ARE USED, THE CORRESPOND- |
| ING PRODUCT APPROVALS MUST BE SUBMITTED. |
| MANUFACTURER'S SPECIFICATIONS AND LIST- |
| ING INFORMATION IS REQUIRED IF OPTIONAL |
| BBQ IS INSTALLED. |
| |
| 4) PROVIDE PRODUCT APPROVALS, KEY PLAN |
| AND INSTALLATION SCHEDULE FOR STORM |
| PANELS UNDER A SEPARATE PERMIT. |
| |
| |
| TRUSSES |
| UNSAT |
| |
| 1) THE TRUSS ENGINEERS TITLE BLOCK (NAME |
| ADDRESS AND NUMBER) IS REQUIRED ON THE |
| TRUSS LAYOUT. |
| |
| 2) THE TRUSS DRAWINGS REFERENCE |
| INCORRECT DESIGN CRITERIA (ASCE 7-93), |
| THE PROPER CRITERIA IS ASCE 7-95 WITH |
| (145 MPH WINDLOAD) OR 1997 SBC SECTION |
| 1606 WITH (110 MPH WINDLOAD). PLEASE |
| CORRECT. |
| |
| 3) THE TRUSS DETAILS FOR BRACING, GABLES |
| OVERHANG, PIGGYBACKS, ETC. |
| |
| 4) TRUSS DRAWINGS TG33, T34 AND T35 ARE |
| NOT SHOWN ON THE TRUSS LAYOUT AND THERE |
| ARE NO TRUSS DRAWINGS FOR TRUSSES TG31, |
| T32 AND T33 WHICH ARE INDICATED ON THE |
| TRUSS LAYOUT. PLEASE CORRECT. |
| |
| 5) THERE ARE TWO TRUSS DRAWINGS FOR THE |
| SAME TRUSS WITH DIFFERENT UPLIFT VALUES |
| LISTED. PLESAE CORRECT. |
| |
| NOTE: |
| THESE COMMENTS APPLY TO THE FOLLOWING |
| PERMIT NUMBERS: 01060846, 01060847, |
| 01060848, 01060849. |