2001-07-24 00:00:00 | *************BUILDING UNSAT************* |
| |
| 1) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) THE PLANS INDICATE A 50 GALLON WATER |
| HEATER AND THE ENERGY CALCULATIONS LIST |
| A 40 GALLON WATER HEATER. PLEASE |
| CORRECT. |
| |
| 3) |
| NOTE:IF OPTIONS ARE USED,THE CORRESPOND- |
| ING PRODUCT APPROVALS MUST BE SUBMITTED. |
| (DOUBLE FRENCH DOORS, FRENCH DOOR WITH |
| SIDELITES) PROVIDE MANUFACTURERS SPECS |
| AND LISTING INFORMATION IF OPTIONAL BBQ |
| IS TO BE INSTALLED. |
| |
| 4) PROVIDE (2) PRODUCT APPROVALS, KEY |
| PLANS AND INSTALLATION SCHEDULES |
| INDICATING THE SPECIFIC TYPES OF ANCHORS |
| TO BE USED FOR STORM PANELS OR APPLY |
| UNDER A SEPARATE PERMIT. |
| |
| 5) STRUCTURE IS LOCATED IN AN AO FLOOD |
| ZONE. AN ELEVATION CERTIFICATE WILL BE |
| REQUIRED. |
| |
| 6) PLEASE INDICATE THE MEAN ROOF HEIGHT |
| OF THE STRUCTURE. |
| |
| 7) PROVIDE A DESIGN COMPLIANCE FORM |
| COMPLETED BY THE DESIGNER OF RECORD FOR |
| THE STRUCTURE OR PROVIDE THE REQUIRED |
| DESIGN PARAMETERS AND ASSUMPTIONS ON THE |
| PLANS. |
| |
| 8) THE UPLIFT VALUES FROM THE TRUSS |
| DRAWINGS EXCEED THE ANCHOR CAPACITIES |
| LISTED ON THE PLANS FOR THE FOLLOWING |
| TRUSSES: T7,T8,T10,T11,T12,T13,T14,T15, |
| T21,T22,T24,T25,T28,T29,T30,T31. PLEASE |
| REVIEW AND CORRECT. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)659-8096 EXT.8202 |
| |
| |
| TRUSSES |
| UNSAT |
| |
| 1) THE BLOCK STAMP OF THE TRUSS ENGINEER |
| IS REQUIRED ON THE TRUSS LAYOUT. |
| |
| 2) THE DETAIL DRAWINGS FOR BRACING, |
| GABLES, OVERHANG, PIGGYBACK, ETC. ARE |
| NOT SIGNED SEALED AND DATED BY THE |
| ENGINEER. THESE DRAWINGS ALSO REFRENCE |
| ASCE 7-93 AND 110 MPH WINDSPEED. THE 97 |
| SBC REQUIRES THE DESIGN CRITERIA TO |
| COMPLY WITH SECTION 1606 (110 MPH WIND- |
| LOAD) OR ASCE 7-95 (145 MPH WINDLOAD). |
| PLEASE CORRECT. |
| |
| 3) THE TRUSS LAYOUT LISTS ASCE 7-95 AND |
| 140 MPH. THE WINDLOAD FOR W.P.B. IS |
| 145 MPH BY LINEAR INTERPOLATION OF WIND |
| SPEED CONTOUR LINES. PLEASE CORRECT. |
| |
| 4) TRUSS DRAWINGS TG33,T34 AND T35 ARE |
| NOT SHOWN ON TRUSS LAYOUT. THE LAYOUT |
| HAS TG31, T32 AND T33 AND NO CORRESPOND- |
| ING DRAWINGS. PLEASE CLARIFY. PLEASE |
| PROVIDE AN INDEX OF TRUSS DRAWINGS. |
| |
| |
| NOTE: |
| THESE COMMENTS APPLY TO THE FOLLOWING |
| PERMIT NUMBERS: 01060846, 01060847, |
| 01060848, 01060849. |