Date Text
2001-09-10 00:00:00************BUILDING PROVISO************
  
 1)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - GARAGE DOORS (PRIOR TO INSTALLATION)
  
 2) STRUCTURE IS LOCATED IN AN AO FLOOD
 ZONE AN ELEVATION CERTIFICATE IS
 REQUIRED.
  
 3) IF OPTIONS ARE USED, THE CORRESPOND-
 ING PRODUCT APPROVALS MUST BE SUBMITTED.
 THE MANUFACTURER'S SPECIFICATIONS AND
 LISTING INFORMATION IS REQUIRED IF
 OPTIONAL BBQ IS INSTALLED.
  
 4) PROVIDE PRODUCT APPROVALS, KEY PLAN
 AND INSTALLATION SCHEDULE FOR STORM
 PANELS UNDER A SEPARATE PERMIT.
  
  
 TRUSSES
 UNSAT
  
 1)THE TRUSS ENGINEERS TITLE BLOCK (NAME,
 ADDRESS AND REGISTRATION NUMBER) IS
 REQUIRED ON THE TRUSS LAYOUT.
  
 2) THE (2) TRUSS LAYOUTS THAT WERE
 SUBMITTED ARE DIFFERENT. SOME OF THE
 TRUSSES ARE LABELED DIFFERENTLY. PLEASE
 SUBMIT (2) LAYOUTS THAT ARE THE SAME.
  
 3) THE TRUSS DRAWINGS ALSO DIFFER. ONE
 SET OF DRAWINGS INCORRECTLY REFERENCES
 ASCE 7-93 AND LISTS DIFFERENT MEAN ROOF
 HEIGHTS. THE OTHER SET ALSO HAS SOME
 DISCREPANCIES WITH MEAN ROOF HEIGHT AND
 REFERS TO 1997 SBCC. THE PROPER
 REFERENCE IS 1997 STANDARD BUILDING CODE
 (1997 SBC). PLEASE CORRECT.
  
 4) THE TRUSS DRAWINGS FOR GABLE DETAILS,
 OVERHANG, PIGGYBACKS, ETC. DO NOT HAVE
 THE EMBOSSED SEAL, WET SIGNATURE AND
 DATE BY THE TRUSS ENGINEER. THESE ALSO
 REFERENCE OUTDATED OR INCORRECT DESIGN
 CRITERIA (ASCE7-88, ASCE7-93, 1991 SBC).
 PLEASE CORRECT.
  
 NOTE:
 THESE COMMENTS APPLY TO THE FOLLOWING
 PERMIT NUMBERS: 01060842,01060843,
 01060844,01060845.