2001-07-25 00:00:00 | *************BUILDING UNSAT************* |
| |
| 1) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) THE PLANS INDICATE A 50 GAL. WATER |
| HEATER AND THE ENERGY CALCULATIONS LIST |
| A 40 GAL. WATER HEATER. PLEASE CORRECT. |
| |
| 3) NOTE: IF OPTIONS ARE USED, THE |
| CORRESPONDING PRODUCT APPROVALS MUST BE |
| SUBMITTED FOR FRENCH DOORS. IF OPTIONAL |
| BBQ IS TO BE INSTALLED, PROVIDE MANUFAC- |
| TURERS SPECIFICATIONS AND LISTING INFOR- |
| MATION. |
| |
| 4) PROVIDE (2) PRODUCT APPROVALS, KEY |
| PLANS AND INSTALLATION SCHEDULES |
| INDICATING THE SPECIFIC TYPES OF ANCHORS |
| TO BE USED FOR STORM PANELS. |
| |
| 5)STRUCTURE IS LOCATED IN AN AO FLOOD |
| ZONE. A FLOOD ELEVATION CERTIFICATE WILL |
| BE REQUIRED. |
| |
| 6) INDICATE THE MEAN ROOF HEIGHT OF THE |
| STRUCTURE. |
| |
| 7) PLEASE PROVIDE A DESIGN COMPLIANCE |
| FORM COMPLETED BY THE DESIGNER OF RECORD |
| FOR THE STRUCTURE. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)659-8096 EXT.8202 |
| |
| |
| TRUSSES |
| UNSAT |
| |
| 1) THE BLOCK STAMP OF THE TRUSS ENGINEER |
| IS REQUIRED ON THE TRUSS LAYOUT. |
| |
| 2) THE TRUSS DETAIL DRAWINGS FOR GABLES, |
| OVERHANG,ETC.ARE NOT SIGNED BY THE DATED |
| BY THE TRUSS ENGINEER. THESE DRAWINGS |
| ALSO REFERENCE INCORRECT DESIGN CRITERIA |
| THE 97 STANDARD BUILDING CODE AS ADOPTED |
| BY THE CITY OF WEST PALM BEACH REQUIRES |
| THE DESIGN CRITERIA TO COMPLY WITH SECT. |
| 1606 (110 MPH WINDLOAD) OR ASCE 7-95 |
| (145 MPH WINDLOAD). PLEASE CORRECT. |
| |
| 3) THE (2) TRUSS LAYOUTS SUBMITTED ARE |
| NOT THE SAME. DIFFERENT TRUSS |
| IDENTIFICATIONS ARE GIVEN FOR THE SAME |
| TRUSSES. PLEASE CORRECT. |
| |
| 4) THE MEAN ROOF HEIGHTS LISTED ON THE |
| TRUSS DRAWINGS ARE NOT CONISTENT. THEY |
| SHOULD ALL BE THE SAME AS THE MEAN ROOF |
| HEIGHT OF THE STRUCTURE. |
| |
| 5) THE DESIGN WINDLOAD ON THE TRUSS |
| DRAWINGS LISTS 110 MPH SBCC 1997. PLEASE |
| CORRECT TO SBC 1997 (STANDARD BUILDING |
| CODE). |