2001-07-25 00:00:00*************BUILDING UNSAT*************
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE PLANS INDICATE A 50 GAL. WATER
 HEATER AND THE ENERGY CALCULATIONS LIST
 A 40 GAL. WATER HEATER. PLEASE CORRECT.
  
 3) NOTE: IF OPTIONS ARE USED, THE
 CORRESPONDING PRODUCT APPROVALS MUST BE
 SUBMITTED FOR FRENCH DOORS. IF OPTIONAL
 BBQ IS TO BE INSTALLED, PROVIDE MANUFAC-
 TURERS SPECIFICATIONS AND LISTING INFOR-
 MATION.
  
 4) PROVIDE (2) PRODUCT APPROVALS, KEY
 PLANS AND INSTALLATION SCHEDULES
 INDICATING THE SPECIFIC TYPES OF ANCHORS
 TO BE USED FOR STORM PANELS.
  
 5)STRUCTURE IS LOCATED IN AN AO FLOOD
 ZONE. A FLOOD ELEVATION CERTIFICATE WILL
 BE REQUIRED.
  
 6) INDICATE THE MEAN ROOF HEIGHT OF THE
 STRUCTURE.
  
 7) PLEASE PROVIDE A DESIGN COMPLIANCE
 FORM COMPLETED BY THE DESIGNER OF RECORD
 FOR THE STRUCTURE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202
  
  
 TRUSSES
 UNSAT
  
 1) THE BLOCK STAMP OF THE TRUSS ENGINEER
 IS REQUIRED ON THE TRUSS LAYOUT.
  
 2) THE TRUSS DETAIL DRAWINGS FOR GABLES,
 OVERHANG,ETC.ARE NOT SIGNED BY THE DATED
 BY THE TRUSS ENGINEER. THESE DRAWINGS
 ALSO REFERENCE INCORRECT DESIGN CRITERIA
 THE 97 STANDARD BUILDING CODE AS ADOPTED
 BY THE CITY OF WEST PALM BEACH REQUIRES
 THE DESIGN CRITERIA TO COMPLY WITH SECT.
 1606 (110 MPH WINDLOAD) OR ASCE 7-95
 (145 MPH WINDLOAD). PLEASE CORRECT.
  
 3) THE (2) TRUSS LAYOUTS SUBMITTED ARE
 NOT THE SAME. DIFFERENT TRUSS
 IDENTIFICATIONS ARE GIVEN FOR THE SAME
 TRUSSES. PLEASE CORRECT.
  
 4) THE MEAN ROOF HEIGHTS LISTED ON THE
 TRUSS DRAWINGS ARE NOT CONISTENT. THEY
 SHOULD ALL BE THE SAME AS THE MEAN ROOF
 HEIGHT OF THE STRUCTURE.
  
 5) THE DESIGN WINDLOAD ON THE TRUSS
 DRAWINGS LISTS 110 MPH SBCC 1997. PLEASE
 CORRECT TO SBC 1997 (STANDARD BUILDING
 CODE).