Plan Review Notes For Permit 01060828 |
Permit Number |
01060828 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-06-20 00:00:00 | 1) A SINGLE MEANS OF EGRESS IS NOT | | PERMITTED FROM EXISTING STORAGE SPACE. | | AT LEAST TWO MEANS OF EGRESS ARE | | REQUIRED SINCE EXCEPTIONS FOR A SINGLE | | MEANS OF EGRESS DOES NOT APPLY | | ACCORDING TO THE DRAWINGS THAT WERE | | SUBMITTED. | | 2) PLEASE PROVIDE A SECOND MEANS OF | | EGRESS FROM THE BUILDING THAT IS AT | | LEAST 1/2 THE DIAGONAL DISTANCE FROM | | THE EXISTING ONE. | | 3) PLEASE IDENTIFY LOCATIONS OF EXIT | | SIGNS AND EMERGENCY LIGHTING EQUIPMENT. | | | | CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|