Plan Review Notes For Permit 01060828 |
Permit Number |
01060828 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-06-28 00:00:00 | ***************** UNSAT ************* | | | | 1)NOTE: PLEASE NOTE THAT NO LIGHTING IS | | SHOWN. EXIT/EGRESS. ETC 210-70 | | | | 2)NOTE: PLEASE NOTE THAT PLANS NEED TO | | SHOW ALL BRANCH CIRCUIT #`S ON PLANS | | AND NEED TO CORRELATE W/ PANEL SCHEDULE | | 215-5 | | | | 3)NOTE: PLEASE NOTE THAT LOAD | | CALCULATIONS DO NOT SHOW ANY OTHER | | LOADS. | | | | PLEASE SUBMIT MORE INFORMATION FOR | | REVIEW. IF THERE AREANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|