Plan Review Notes
Plan Review Notes For Permit 01060828
Permit Number 01060828
Review Stop B
Sequence Number 1
Notes
Date Text
2001-07-04 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01060828
 2805-A PINEWOOD AVE
 CONT: ALLIANCE CONST.
 PHONE: 748-9135
  
 1)- IN REVIEWING THIS PLAN THE 1997
 STANDARD BUILDING CODE DOES NOT ALLOW
 A WAREHOUSE OF 3150 SQ FT TO HAVE A SIN-
 GLE MEANS OF EGRESS.
 SBC 1027.1.1 SINGLE EXIT REQUIREMENTS
 FOR STORAGE OCCUPANCY:
 1- ONE STORY MAXIMUM
 2- THE FLOOR AREA DOES NOT EXCEED
 2,500 SQ FT
 3- THE MAXIMUM DISTANCE OF TRAVEL TO
 THE EXIT DOES NOT EXCEED 50 FT.
  
 2)- SBC 1004.1.4: WHERE 2 OR MORE EXITS
 OR EXIT DOORS ARE REQUIRED, AT LEAST 2
 EXITS OR EXIT ACCESS DOORS SHALL BE
 PLACED A DISTANCE AAPART EQUAL TO BUT
 NOT LESS THAN ONE HALF THE LENGTH OF THE
 MAXIMUMOVERALL DIAGONAL DIMENSION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412