Plan Review Notes For Permit 01060821 |
Permit Number |
01060821 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-06-19 00:00:00 | ******************PROVISO*************** | | | | | | REVIEW COMMENTS DATED 2/24/01 UNDER | | MASTER PERMIT 01011120. | | | | | | 1.SHOW SIZE AND LOCATION OF R/A | | (SHOULD BE IN CENTER ROOM). | | | | 2.SHOW DUCT SIZE TO DROP IN ROOM THAT | | AIR HANDLER IS IN. | | | | 3.SHOW LOCATION OF CONDENSER UNIT. | | CONDENSER SHALL BE ON A SOLID | | CONCRETE SLABE MINIMUM 3" ABOVE | | THE ADJOINING GROUND LEVEL. | | | | NOTE:REVISED DRAWINGS REQUIRED PRIOR | | TO THE ROUGH INSPECTION. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | PATTY KRAUSS AT 659-8096 EXT.8388. |
|