Plan Review Notes For Permit 01060716 |
Permit Number |
01060716 |
|
Review Stop |
R |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2001-11-14 00:00:00 | TRUSS DRAWINGS CHECKLIST: | | 1-ENGINEERED TRUSSES ARE DESIGNED USING | | DIFFERENT MEAN ROOF HEIGHTS. THERE IS | | ONLY ONE MEAN ROOF HEIGHT FOR ENTIRE | | BUILDING. REVIEW ALL ENGINEERED | | TRUSSES AND REVISE AS REQUIRED. | | TABLE 1606.2A SBC 1997. | | 2-SOME TRUSSES ARE DESIGNED USING WALL | | HEIGHT. THIS APPLIES TO A FLAT ROOF. | | USE MEAN ROOF HEIGHT FOR SLOPED ROOF. | | REVISED AS REQUIRED. | | 3-GENERAL DETAILS: | | A)THERE ARE TWO DIFFERENT ENGINEERS. | | COMPLY WITH REQUIREMENTS OF CHAPTER | | 471 FL. STATUTES WHEN CHANGING ENG'R. | | B)UPDATE GENERAL DETAILS DESIGN CRITERIA | | C)DETAILS AND SPECS ARE NOT LEGIBLE. | | | | | | NOTES: | | -THESE COMMENTS HAVE BEING ADDRESSED ON | | PREVIOUS REVIEWS. | | -DRAWINGS TO BE FILED UNDER PERMIT # | | 01060716, 01060718, 01060721 AND | | 01060723. |
|