Plan Review Notes
Plan Review Notes For Permit 01060598
Permit Number 01060598
Review Stop E
Sequence Number 1
Notes
Date Text
2001-06-24 00:00:00******************* UNSAT *************
  
 1)NOTE: PLEASE NOTE THAT PLANS ARE
 SHOWING SM APPLIANCE CIRCUTIS AT 5000W`S
 PLEASE NOTE THAT SM APPL IS REQ`D AT
 1500KW PER CIRCUIT. PLEASE CORRECT
  
 2)NOTE: PLEASE NOTE THAT LOAD SHOWN FOR
 GARAGE DOOR OPENERS EXCEED 80% OF 15A
 BRKR.
  
 3)NOTE: PLEASE NOTE THAT PLANS SHOW WELL
 PUMP AND PANEL SCHEDULE SHOWS SPRINKLER
 VALVE. PLEASE CLARIFY.
  
 4)NOTE: PLEASE NOTE THAT THE GFI NOTE
 ON PLANS IN REF TO GFI`S IN KITCHEN IS
 NO LONGER.(93 NEC). PLEASE NOTE THAT ALL
 RECEPTS SERVING KITCHEN COUNTERSPACE ARE
 TO BE GFI/GFI PROTECTED. PER 210-8-A-6.
  
 5) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 6)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 7)NOTE: PLEASE NOTE THAT RISER IS SHOWIN
 G AN EQUIPMENT GROUNDING CONDUCTOR
 BETWEEN METER AND FIRST MEANS OF DISCO-
 -NNECT. PLEASE NOTE THAT THIS WOULD BE
 PARALLELING THE NEUTRAL.
  
 8) PLEASE NOTE MISSING OUTLET FOR A/C
 EQUIPMENT PER 210-63 OF NEC AND 309.1
 MECHANICAL CODE.
  
 9)NOTE: PLEASE NOTE THAT PLANS ARE SHOW-
 -ING TWO METERS? PLEASE CLARIFY.
 IS SECOND LOCATION OPTIONAL?
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372