2001-06-24 00:00:00 | ******************* UNSAT ************* |
| |
| 1)NOTE: PLEASE NOTE THAT PLANS ARE |
| SHOWING SM APPLIANCE CIRCUTIS AT 5000W`S |
| PLEASE NOTE THAT SM APPL IS REQ`D AT |
| 1500KW PER CIRCUIT. PLEASE CORRECT |
| |
| 2)NOTE: PLEASE NOTE THAT LOAD SHOWN FOR |
| GARAGE DOOR OPENERS EXCEED 80% OF 15A |
| BRKR. |
| |
| 3)NOTE: PLEASE NOTE THAT PLANS SHOW WELL |
| PUMP AND PANEL SCHEDULE SHOWS SPRINKLER |
| VALVE. PLEASE CLARIFY. |
| |
| 4)NOTE: PLEASE NOTE THAT THE GFI NOTE |
| ON PLANS IN REF TO GFI`S IN KITCHEN IS |
| NO LONGER.(93 NEC). PLEASE NOTE THAT ALL |
| RECEPTS SERVING KITCHEN COUNTERSPACE ARE |
| TO BE GFI/GFI PROTECTED. PER 210-8-A-6. |
| |
| 5) NOTE: PLEASE LIST THE REQ`D BATH(S) |
| CIRCUIT(S) PER 210-11-C-3. |
| MUST BE 20A AND #12AWG. |
| |
| 6)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW EQUIPMENT BEING INSTALLED. |
| MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| THE AVAILABLE FAULT CURRENT PER 110-9. |
| |
| 7)NOTE: PLEASE NOTE THAT RISER IS SHOWIN |
| G AN EQUIPMENT GROUNDING CONDUCTOR |
| BETWEEN METER AND FIRST MEANS OF DISCO- |
| -NNECT. PLEASE NOTE THAT THIS WOULD BE |
| PARALLELING THE NEUTRAL. |
| |
| 8) PLEASE NOTE MISSING OUTLET FOR A/C |
| EQUIPMENT PER 210-63 OF NEC AND 309.1 |
| MECHANICAL CODE. |
| |
| 9)NOTE: PLEASE NOTE THAT PLANS ARE SHOW- |
| -ING TWO METERS? PLEASE CLARIFY. |
| IS SECOND LOCATION OPTIONAL? |
| |
| |
| PLEASE SUBMIT ALL THE ABOVE INFORMATION |
| FOR REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-659-8096 EXT 8372 |