2001-07-19 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT # 01060598 |
| 295 QUEEN CT. |
| CONT: BILL FREE & ASSOC. INC. |
| (561) 624-0149 |
| |
| 1)- FL. ENERGY CALCULATIONS INCLUDING |
| MANUAL "J". |
| 2)- SHEET A-2 :SECTION#2 FRAMING DETAILS |
| MISSING CRIPPLE STUDS AT THE END OF HEAD |
| ER & CONNECTION TOP PLATE / HEADER. |
| 3)- SHEET A-5 WEST OR LEFT SIDE DETAIL, |
| MISSING INFOR. ON THE WATERPROOFING FOR |
| THE BACK PORCH AND FRONT BALCONY. |
| 4)- SUB SHEATHING NOT TO CODE: SBC 2305. |
| 2.5 FOLLOWING STANDARDS APA MANUAL PAGE |
| 33 FIG. 10-13 DEPICTS SHEATHING TO THE |
| BOTTOM OF THE RIM BOARD WITH THE WOOD |
| SIDING EXTENDING BELOW THAT. |
| 5)-SBC 2303.3 REQUIRES A MOISTURE |
| PROTECTION VAPOR BARRIER. |
| 6)- SHEET A-2 SEC"A" SHOWS A CLEAR |
| SPAN OF 21'-9" OF WINDOW OPENINGS WITH |
| OUT ANY SUPPORT. PLEASE INDICATE THE |
| LOADING THAT IS IMPOSED UPON THIS BEAM |
| GRAVITY LOADS, LIVE / DEAD LOADS OVER |
| THE TRIBUTARY AREA. |
| 7)- THE SOFFIT FACIA DETAIL SECTION A,B, |
| & C INDICATE SOFFITS WITH 5/8" PLYWOOD, |
| PLEASE INDICATE ROOF VENTING. |
| 8)- DISCREPANCY: FLOOR TRUSS CANTILEVER |
| AS IN ITEM #4 SUB-SHEATHING IS NOT CON- |
| TINUED TO THE BOTTOM OF THE FLOOR TRUSS. |
| 8)- J-BOLT SIZE & SPACING IS NOT INDICA- |
| TED ON THE PLAN. |
| 9)- SBC 2304.2 AMEND. CLEARENCE BETWEEN |
| WOOD SIDING & EARTH TO BE A MINIMUM OF |
| 6".(A-6) |
| 10)- SHEET S-2 RAILING DETAIL SBC 1015.3 |
| A SPHERE 4" CAN NOT PASS BETWEEN THE |
| BALISTERS. |
| 11)- PRODUCT APPROVALS: FOR ALL GLAZED |
| OPENINGS PRODUCT TESTING IS REQUIRED FOR |
| LARGE MISSLE IMPACT RESISTANCE TESTING, |
| SBCCI OR DADE COUNTY PRODUCT APPROVAL |
| REPORTS ARE ACCEPTED.SBC 1606.4 AMEND./ |
| 1707.4.1 AMEND. |
| SBC 1606.2.6.2 COMPONENTS& CLADDING: |
| DOORS & GARAGE DOORS ARE REQUIRED TO |
| HAVE PRODUCT TESTING ALSO SBCCI OR DADE |
| COUNTY REPORT. |
| ROOFING SYSTEMS SBC 1503.2. ROOFING ASS- |
| EMBLIES ARE TO HAVE PRODUCT TESTING FOR |
| A 110 MPH WIND ZONE,1705 CLAY OR CEMENT |
| TILE ARE TO BE TESTED FORTHERE MOMENT OF |
| OVERTURNING, DAEE OR SBCCI REPORT. |
| |
| BUILDING PLAN REVIEW |
| JIM WITMER |
| (561)659-8096 X 8412 |