Plan Review Notes
Plan Review Notes For Permit 01060536
Permit Number 01060536
Review Stop E
Sequence Number 1
Notes
Date Text
2001-06-19 00:00:00****************** UNSAT ***************
  
  
 1) PLEASE NOTE EITHER MISSING EGRESS
 LIGHTING AND/OR CLARIFY EGRESS LIGHTING
 PER 210-70 OF THE NEC.
 PLEASE NOTE NUMEROUS ROOMS MISSING
 EGRESS LIGHTING.
  
 2)NOTE: PLEASE NOTE THAT ELECTRICAL NOTE
 -S ON PLANS REFERENCE ART 251-22 FOR
 GROUNDING. PLEASE NOTE THAT THIS MUST BE
 A MISPRINT. PLEASE CHANGES THE ART IS
 250-122 NEC.
  
 3)NOTE: PLEASE NOTE PANEL SCHEDULE "A"
 PLEASE NOTE THAT OCP/BRKR AND WIRE
 SIZES NEED TO CORRELATE. PLEASE NOTE
 THAT YOU SHOW 30A OCP W/ 7000W LOAD?
 AND 50A OCP ON 5000W LOAD? PLEASE ALSO
 NOTE THAT 1- 20A OCP W/ 8OOOW LOAD.
 PLEASE CORRECT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372