Plan Review Notes
Plan Review Notes For Permit 01060458
Permit Number 01060458
Review Stop E
Sequence Number 1
Notes
Date Text
2001-06-13 00:00:00****************** UNSAT ***************
  
  
 1)NOTE: PLEASE NOTE THAT PERMIT APPL
 SAYS INSTALLING NEW ELEC TO GUEST HOUSE?
 PLEASE CLARIFY. PLANS SHOW NEW ELEC IN
 GUEST HOUSE? PLEASE CLARIFY.
  
 2)NOTE: PLEASE NOTE THAT SMOKE DETECTORS
 ARE REQ`D INSIDE AND OUTSIDE BEDROOM
 PER NFPA-72 2-2.1.1.1
  
 3) PLEASE NOTE EITHER MISSING EGRESS
 LIGHTING AND/OR CLARIFY EGRESS LIGHTING
 PER 210-70 OF THE NEC. MAIN ROOM SHOWS
 FAN AND NO LIGHT? PLEASE NOTE ALSO FOR
 EXITING.
  
 4)NOTE: PLEASE CLARIFY PANEL? SHOWN AS
 NEW.? PLEASE SHOW WHERE PANEL IS BEING
 FED FROM AND HOW PANEL IS BEING FED.
 WIRE SIZES ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  