Plan Review Notes For Permit 01060349 |
Permit Number |
01060349 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-07-04 00:00:00 | BUILDING PLAN REVIW | | PERMIT # 01060349 | | 1450 CENTREPARK # 100 | | BURKHARDT CONST | | PHONE 659-1400 | | | | 1)- DOOR 101B DOESN'T INDICATE IF THERE | | IS A RATING ON THIS DOOR, LEADING TO AN | | EXIT ACCESS CORIDOR. | | | | 2)- STANDARD BUILDING CODE 1004.1.1: | | WHERE 2 OR MORE EXITS OR EXIT ACCESS | | DOORS ARE REQUIRED, AT LEAST 2 EXIT OR | | EXIT ACCESS DOORS SHALL BE PLACED A DIST | | ANCE APART EQUALL TO NOT LESS THAN ONE | | HALF THE LENGTH OF THE MAXIMUM OVERALL | | DIAGONAL DIMENSION OF THE UNIT. | | | | 3)- FLORIDA ACC CODE 1997 EDI. 4.5.1: | | GROUND AND FLOOR SURFACES ALONG ACCESSIB | | LE ROUTES AND IN ACCESSIBLE ROOMS & | | SPACES INCLUDING FLOORS RAMPS STAIRS & | | RAMPS SHALL BE STABLE, SLIP RESISTANT & | | SHALL COMPLY WITH 4.5. (ADDAAG A-5) | | THE RECOMMENDED WALKING SURFACES HAVE A | | STATIC COEFFICIENT OF FRICTION OF 0.6 IS | | FOR ACCESSIBLE ROUTES AND 0.8 FOR RAMPS. | | | | BUILDING PLAN REVIEW | | JIM WITMER | | (561) 659-8096 EX 8412 |
|