2001-07-04 00:00:00BUILDING PLAN REVIW
 PERMIT # 01060349
 1450 CENTREPARK # 100
 BURKHARDT CONST
 PHONE 659-1400
  
 1)- DOOR 101B DOESN'T INDICATE IF THERE
 IS A RATING ON THIS DOOR, LEADING TO AN
 EXIT ACCESS CORIDOR.
  
 2)- STANDARD BUILDING CODE 1004.1.1:
 WHERE 2 OR MORE EXITS OR EXIT ACCESS
 DOORS ARE REQUIRED, AT LEAST 2 EXIT OR
 EXIT ACCESS DOORS SHALL BE PLACED A DIST
 ANCE APART EQUALL TO NOT LESS THAN ONE
 HALF THE LENGTH OF THE MAXIMUM OVERALL
 DIAGONAL DIMENSION OF THE UNIT.
  
 3)- FLORIDA ACC CODE 1997 EDI. 4.5.1:
 GROUND AND FLOOR SURFACES ALONG ACCESSIB
 LE ROUTES AND IN ACCESSIBLE ROOMS &
 SPACES INCLUDING FLOORS RAMPS STAIRS &
 RAMPS SHALL BE STABLE, SLIP RESISTANT &
 SHALL COMPLY WITH 4.5. (ADDAAG A-5)
 THE RECOMMENDED WALKING SURFACES HAVE A
 STATIC COEFFICIENT OF FRICTION OF 0.6 IS
 FOR ACCESSIBLE ROUTES AND 0.8 FOR RAMPS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412