Plan Review Notes
Plan Review Notes For Permit 01060347
Permit Number 01060347
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2001-06-25 00:00:001) UNABLE TO LOCATE EMERGENCY LIGHT
 FIXTURES FOR STORAGE AREA. EMERGENCY
 LIGHT FIXTURES ARE REQUIRED.
 2) AFTER PERFORMING EXIT CALCULATIONS A
 SINGLE EXIT IS NOT PERMITTED. TRAVEL
 DISTANCE EXCEEDS 100 FEET WITH THE
 FIRE SPRINKLER PROVISION BEING INCLUDED.
 PLEASE PROVIDE LOCATION OF SECOND MEANS
 OF EGRESS AND EXIT SIGN LOCATION.
 3) SEPARATE PLANS AND PERMITS REQUIRED
 FOR GENERATOR AND ANY FUEL STORAGE.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910