Plan Review Notes For Permit 01060347 |
Permit Number |
01060347 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2001-06-24 00:00:00 | ************ UNSAT********** | | | | 1)NOTE: PLEASE NOTE THAT SUBMITTING | | THE AVAILABLE FAULT CURRENT FROM FPL | | DOESN'T TELL ME WHAT YOUR EQUIPMENT IS | | GOING TO BE RATED AT? PLEASE NOTE THAT | | I WOULD NEED MORE INFORMATION IN ORDER | | TO COME UP WITH A RATING. PLEASE | | ALSO NOTE IF GOING BY FPL LETTER | | MAINS WOULD BE AT 65,000 AND ALL | | EQUIPMENT AND BRKRS WOULD NEED TO BE | | SERIES RATED. ALL PER 110-9. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE AREA ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|