Plan Review Notes
Plan Review Notes For Permit 01060347
Permit Number 01060347
Review Stop E
Sequence Number 2
Notes
Date Text
2001-06-24 00:00:00************ UNSAT**********
  
 1)NOTE: PLEASE NOTE THAT SUBMITTING
 THE AVAILABLE FAULT CURRENT FROM FPL
 DOESN'T TELL ME WHAT YOUR EQUIPMENT IS
 GOING TO BE RATED AT? PLEASE NOTE THAT
 I WOULD NEED MORE INFORMATION IN ORDER
 TO COME UP WITH A RATING. PLEASE
 ALSO NOTE IF GOING BY FPL LETTER
 MAINS WOULD BE AT 65,000 AND ALL
 EQUIPMENT AND BRKRS WOULD NEED TO BE
 SERIES RATED. ALL PER 110-9.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE AREA ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372