2001-06-12 00:00:00 | ************** UNSAT ***************** |
| |
| 1)NOTE: PLEASE NOTE THAT UNDER F.S. AND |
| F.A.C. ALL PLAN DONE BY AN ARCH/ENGINEER |
| MUST BE SIGNED,DATED AND SEALED BY THE |
| ARCH/ENG OF RECORD. 471.025 AND 481.221 |
| |
| 2)NOTE: PLEASE NOTE LOCATION OD GENERAT- |
| -OR NOT SHOWN? |
| |
| 3)NOTE: PLEASE NOTE GROUPING OF DISCONNE |
| CTS FOR MAIN AND GENERATOR.230-72 ALSO |
| PLEASE NOTE 230-76 AND 230-79. |
| |
| 4) NOTE: PLEASE SHOW CALCULATIONS FOR |
| TRACK LIGHTING PER 220-12B. |
| |
| 5) NOTE: PLEASE SHOW ALL CONTINUOUS AT |
| 125%. (LIGHTING ETC) |
| |
| |
| 6)NOTE: PLEASE CLARIFY 8 CIRCUITS SHOWN |
| FOR BATTERY CHARGER?? |
| |
| 7)NOTE: PLEASE SHOW LOAD CALCULATIONS |
| PER 220. SQ.FT ETC. |
| |
| 8)NOTE: PLEASE SHOW GROUNDING ELECTRODE |
| GOING TO BUILDING STEEL AND COLD WATER |
| PER 250-50.GROUND ROD AND COLD WATER |
| IF BLDG STEEL IS NOT AVAILABLE. |
| |
| 9)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW EQUIPMENT BEING INSTALLED. |
| MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| THE AVAILABLE FAULT CURRENT PER 110-9. |
| |
| 11)NOTE: PLEASE NOTE THAT OUTLET SPACING |
| NEEDS TO MEET LOCAL CODE 210-50 FOR |
| OUTSIDE WALL IN STORAGE AREA |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| FOR REVIEW. IF THERE ARE ANY QUESTIONS |
| PLEASE CALL. |
| |