2001-06-12 00:00:00************** UNSAT *****************
  
 1)NOTE: PLEASE NOTE THAT UNDER F.S. AND
 F.A.C. ALL PLAN DONE BY AN ARCH/ENGINEER
 MUST BE SIGNED,DATED AND SEALED BY THE
 ARCH/ENG OF RECORD. 471.025 AND 481.221
  
 2)NOTE: PLEASE NOTE LOCATION OD GENERAT-
 -OR NOT SHOWN?
  
 3)NOTE: PLEASE NOTE GROUPING OF DISCONNE
 CTS FOR MAIN AND GENERATOR.230-72 ALSO
 PLEASE NOTE 230-76 AND 230-79.
  
 4) NOTE: PLEASE SHOW CALCULATIONS FOR
 TRACK LIGHTING PER 220-12B.
  
 5) NOTE: PLEASE SHOW ALL CONTINUOUS AT
 125%. (LIGHTING ETC)
  
  
 6)NOTE: PLEASE CLARIFY 8 CIRCUITS SHOWN
 FOR BATTERY CHARGER??
  
 7)NOTE: PLEASE SHOW LOAD CALCULATIONS
 PER 220. SQ.FT ETC.
  
 8)NOTE: PLEASE SHOW GROUNDING ELECTRODE
 GOING TO BUILDING STEEL AND COLD WATER
 PER 250-50.GROUND ROD AND COLD WATER
 IF BLDG STEEL IS NOT AVAILABLE.
  
 9)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 11)NOTE: PLEASE NOTE THAT OUTLET SPACING
 NEEDS TO MEET LOCAL CODE 210-50 FOR
 OUTSIDE WALL IN STORAGE AREA
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  