Plan Review Notes
Plan Review Notes For Permit 01060332
Permit Number 01060332
Review Stop M
Sequence Number 1
Notes
Date Text
2001-06-11 00:00:00*******************DENIED***************
  
 PULL MECH FROM MAIN SET, CMI TO SUBMIT
 PLANS
  
 MECHANICAL PERMIT REQUIRED.PLEASE
 SUBMIT THE FOLLOWING INFORMATION FOR
 REVIEW.
  
 MANUFACTURER/ENGINEER DETAIL OF ROOF
 CURBS.
  
 LOCATION AND TERMINATION OF CONDENSATE.
  
 FAN SHUTDOWN BY DUCT SMOKE DETECTORS
 WITH NOTIFICATION TO ALARM/STROBE IN
 NORMALLY OCCUPIED AREAS. (1997 SMC 406.1
 AND NFPA 90A 4-4.4.3, RESPECTIVELY)
  
 PLEASE PROVIDE OUTSIDE AIR CALCULATIONS
 AS PER ASHRAE 62-89.
  
 PLANS ARE NOT DATED OR SIGNED AND SEALED
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT.8388.