Plan Review Notes For Permit 01060332 |
Permit Number |
01060332 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-06-11 00:00:00 | *******************DENIED*************** | | | | PULL MECH FROM MAIN SET, CMI TO SUBMIT | | PLANS | | | | MECHANICAL PERMIT REQUIRED.PLEASE | | SUBMIT THE FOLLOWING INFORMATION FOR | | REVIEW. | | | | MANUFACTURER/ENGINEER DETAIL OF ROOF | | CURBS. | | | | LOCATION AND TERMINATION OF CONDENSATE. | | | | FAN SHUTDOWN BY DUCT SMOKE DETECTORS | | WITH NOTIFICATION TO ALARM/STROBE IN | | NORMALLY OCCUPIED AREAS. (1997 SMC 406.1 | | AND NFPA 90A 4-4.4.3, RESPECTIVELY) | | | | PLEASE PROVIDE OUTSIDE AIR CALCULATIONS | | AS PER ASHRAE 62-89. | | | | PLANS ARE NOT DATED OR SIGNED AND SEALED | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | PATTY KRAUSS AT 659-8096 EXT.8388. |
|