Plan Review Notes
Plan Review Notes For Permit 01060238
Permit Number 01060238
Review Stop B
Sequence Number 1
Notes
Date Text
2001-06-13 00:00:00CHECKLIST:
 1-ENGINEERED DRAWINGS ARE NOT LEGIBLE.
 SEC. 104.2 CITY AMENDMENTS.
 2-POLY ROOF SYSTEM:
 A)PROVIDE COPIES OF TESTS TO COMPLY
 WITH PROVISIONS OF CHAPTERS 16 AND 17
 B)PROVIDE COMPLETE INFORMATION SHOWING
 MINIMUM DESIGN OF 20PSF LIVE LOAD.
 SECTION 2001 OF CITY AMENDMENTS.SEE
 ATTACHED COPY.
 3-UPDATE ENGINEERED DRAWINGS CLEARLY
 SHOWING THE DESIGN CRITERIA USED:
 SBC 1997 FOR 110MPH OR ASCE 7-95 FOR
 145MPH.
 4-AS REQUIRED BY CHAPTER 471 OF FLORIDA
 STATUTES, ENGINEER TO PROVIDE:
 A)PROFESSIONAL LICENSE NUMBER.
 B)ORIGINAL SIGNATURE.
 C)DATE WHEN DRAWINGS WERE SEALED.
  
 5-SHEET ONE AND SHEET TWO OF ENGINEERED
 DRAWINGS SHOW DIFFERENT SIZES OF
 CONCRETE FASTENERS. CLARIFY WHY.
 6-ENGINEER TO SEE ATTACHED COPY OF SEC.
 2001 OF CITY AMENDMENTS TO VERIFY THAT
 ALL SPECIAL PROVISIONS ARE MET IN HIS
 DESIGN.
 7-ADDITIONAL FEE OF $2.54 ARE DUE FOR
 RADON FEES.
 8-INDICATE ROOF SLOPE.
 1/4 INCH/FT MIN. SEC 1503.1.2.3 SBC/97