2001-06-13 00:00:00CHECKLIST:
 1-ENGINEERED DRAWINGS ARE NOT LEGIBLE.
 SEC. 104.2 CITY AMENDMENTS.
 2-POLY ROOF SYSTEM:
 A)PROVIDE COPIES OF TESTS TO COMPLY
 WITH PROVISIONS OF CHAPTERS 16 AND 17
 OF SBC 1997.
 B)PROVIDE COMPLETE INFORMATION SHOWING
 MINIMUM DESIGN OF 20PSF LIVE LOAD.
 SECTION 2001 OF CITY AMENDMENTS. SEE
 ATTACHED COPY.
 3-UPDATE ENGINEERED DRAWINGS CLEARLY
 SHOWING THE DESIGN CRITERIA USED:
 SBC 1997 FOR 110MPH OR ASCE 7-95 FOR
 145MPH.
 4-AS REQUIRED BY CHAPTER 471 OF FLORIDA
 STATUTES, ENGINEER TO PROVIDE:
 A)PROFESSIONAL'S LICENCE NUMBER.
 B)ORIGINAL SIGNATURE.
 C)DATE WHEN DRAWINGS WERE SEALED.
  
 5-ENGINEER TO SEE ATTACHED COPY OF SEC.
 2001 OF CITY AMENDMENTS TO VERIFY THAT
 ALL SPECIAL PROVISIONS ARE MET IN HIS
 DESIGN.
 6-ADDITIONAL FEE OF $1.74 ARE DUE FOR
 RADON FEES.
 7-INDICATE ROOF SLOPE.
 1/4 INCH/FT MIN. SEC 1503.1.2.3 SBC/97