Plan Review Notes For Permit 01060176 |
Permit Number |
01060176 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-06-06 00:00:00 | 1) PLANS INDICATE THAT THE FIRE | | SUPPRESSION SYSTEM IS FOR A VEHICLE | | PAINT SPRAY BOOTH. THIS OFFICE HAS | | BEEN ADVISED THAT THE BOOTH WILL BE | | USED TO PAINT FURNITURE NOT VEHICLES. | | 2) PLEASE PROVIDE MORE DETAILS ON TIME | | DELAY NOZZLE. PLEASE PROVIDE CODE | | REFERENCE FOR THIS INSTALLATION. | | 3) PLEASE INDICATE ON PLANS THAT THEY | | MEET NFPA 17, THE STANDARD FOR DRY | | CHEMICAL EXTINGUISHING SYSTEMS. | | | | CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|