Plan Review Notes
Plan Review Notes For Permit 01051401
Permit Number 01051401
Review Stop R
Sequence Number 1
Notes
Date Text
2001-07-06 00:00:00*************BUILDING UNSAT*************
  
 STRUCTURE IS LOCATED IN AN A ZONE, AN
 ELEVATION CERTIFICATE WILL BE REQUIRED.
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) FOUNDATION PLAN ON SHEET 1 INDICATES
 A 16"X 16" FOOTING AND WALL SECTION ON
 SHEET 5 SHOWS A 12"X 16" FOOTING.PLEASE
 CORRECT.
  
 3) THE FOOTINGS ARE NOT INDICATED ON THE
 FOUNDATION PLAN FOR THE BLOCK COLUMNS AT
 THE COVERED ENTRY. THE WALL LINES ARE
 MISSING IN A COUPLE OF PLACES. PLEASE
 CORRECT.
  
 4) PROVIDE MANUAL "J" CALCULATIONS AS
 REQUIRED BY THE FL.ENERGY EFFICIENCY
 CODE 607.1.ABC.1.