2001-06-11 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT # 01051002 |
| 222 LAKEVIEW SUITE # 1600 |
| CATALFUMO CONT. |
| P 694-3000 |
| |
| 1)- TITLE SHEET CODE COMPLIANCE & EGRESS |
| NOTES: FINISH MATERIALS COMPLY WITH |
| FLAME SPREAD RATING AS REQUIRED BYTHE |
| STANDARD BUILDING CODE, 1997 EDITION. |
| |
| 2)- NOTE # 1 REFERS BACK TO SBC CHAPTER |
| 23 FOR MINIMUM ALLOWANCE 5 LBS./ SQ FT |
| LATERAL LOAD REQUIREMENTS, THERE IS NO |
| 2305.9 AS STATED ON PLANS. |
| |
| 3)- HANDICAPPED BARRIERS PER PLAN |
| SBC SECTION 4.1.6/4.1.9 SHOULD READ 1997 |
| FLORIDA ACCESSIBILITY CODE FOR BUILDING |
| CONSTRUCTION. |
| |
| 4)- SHEET 01 LEGEND: PARTITION TYPE 1 |
| LIST UL LISTING OR GYPSUM ASSOC # FOR |
| ASSEMBLY ALSO INDICATE STANDARD BUILDING |
| CODE 704.2 INTERIOR WALLS & PARTITION |
| FIRE SEPERATION REQUIREMENTS. |
| |
| 5)- SBC 704.2.1.4 CORRIDOR PARTITIONS |
| SHALL BE EFFECTIVELY & PERMANETLY WITH |
| SIGN OR STENCILING IN A MANNER ABOVE ANY |
| DECORATIVE CEILING OR CONSEALED SPACE |
| "FIRE & SMOKE BARRIER PROTECT ALL OPEN-I |
| NGS". |
| |
| 6)- SBC 609.2.1. TYPE I & TYPE II BUILD- |
| INGS REQUIRE ALL WOOD IN PARTITIONS, |
| FIRE TREATED WOOD. |
| |
| 7)- SHEET 49.01. MISSING IS THE MINIMUM |
| INTERIOR FINISH CLASSIFICATION SCHEDULE |
| SBC TABLE 803.3. |
| |
| 8)- SBC 412.9 MANUAL FIRE ALARM BOXES |
| SHALL BE PROVIDED. |
| |
| 9)- FIRE SPRINKLERS SBC 412.10 HI-RISE |
| TYPE BUILDINGS REQUIRE FIRE SPRINKLERS. |
| |
| BUILDING OLAN REVIEW |
| JIM WITMER |
| (561) 659-8096 EX 8412 |