2001-06-27 00:00:00************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT PLANS ARE NOW
 BEING SUBMITTED SHOWING NEW MAIN DISC0-
 -NNECT AT HOUSE. PLEASE NOTE THAT AIC
 RATINGS OF ALL NEW EQUIPMENT IS REQ`D
 PER 110-9 AND 215-5.
  
 2)NOTE: PLEASE NOTE THAT PLANS DO NOT
 SHOW EQUIPMENT GROUNDING CONDUCTOR FROM
 HOUSE TO DETACHED STRCTURE PER 250-32.
  
 3)NOTE: PLEASE CLARIFY MAIN DISCONNECT
 BEING SHOWN AT 75AMPS. THIS IS NOT A
 STANDARD EQUIPMNET SIZE. IS THIS100A
 EQUIPMENT W/ 75A FUSES? PLEASE VERFIY
 EQUIPMENT AT HOUSE AND DETACHED STRUC.
  
 4)NOTE: PLEASE NOTE THAT LOADS SHOWN FOR
 BOTH PANELS EXCEED EXISTING 200A METER.
 PLEASE NOTE THAT LOAD CALCULATIONS CAN
 BE ADDED AND FIGURED THAT WAY. THIS IS
 AFTER LOADS ARE FIGURED FOR EACH PANEL.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  