Plan Review Notes
Plan Review Notes For Permit 01050998
Permit Number 01050998
Review Stop E
Sequence Number 1
Notes
Date Text
2001-06-11 00:00:00***************** UNSAT **************
  
 1)NOTE: PLEASE CALRIFY EQUIPMENT AND
 OCP AT DETACHED BLDG? PANEL SCHEDULE
 SHOWS 100A MAIN AND RISER SHOWS 75A
 MAINALSO SHOWS 1/0 WIRE FOR 150A FEED?
  
  
 2)NOTE: PLEASE NOTE THAT LOADS SHOWN
 FOR EXISTING 200A MAIN AND NEW LOAD
 BEING ADDED EXCEEDS RATING OF MAIN.
 PLEASE NOTE THAT LOAD ADDS UP TO 203.2
 AMPS.
 ALSO PLEASE NOTE THAT MAIN PANEL
 SCHEDULE DOES NOT LIST ANY BRKR FEEDING
 DETACHED BLDG.?
  
 3)NOTE: PLEASE CLARIFY APPLIANCE CIRCUIT
 BEING SHOWN AT 15A FOR DETEACHED BLDG.
  
 4) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 5)NOTE: PLEASE CLARIFY IF BOTH MAINS
 AT DETACHED BLDG IS BEING INSTALLED.
 PLANS SHOW MCB AND DISCONNECT ON THE OUT
 SIDE OF STRUCTURE?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372