2001-06-07 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01050966
 1 N. CLEMATIS SUITE 5TH FLOOR
  
 1)- A SUITE # WILL BE REQUIRED TO
 COMPLETE THE ADDRESS.
  
 2)- FL ACCESSIBILITY CODE: OFFICE #4
 SHEET A2-E REQUIRES 18" CLEARENCE PER
 FL ACC CODE 4.13.6.
  
 3)- SHEET A6-E DETAIL #7 PER U-465 UL
 LISTING, STUD SPACING NOT GIVEN.
  
 4)- SHEET A6-E DEAIL #7 CORRIDOR PARTI-
 TIONS & FIRE RATED WALLS REQUIRED TO
 HAVE PROTECTED OPENINGS SHALL PERMANETLY
 IDENTIFY WITH SIGNS OR STECLING "FIRE &
 SMOKE BARRIER PROTECT ALL OPENINGS".
  
 5)- SBC 704.2.1.2. DETAILS 6& 7 OF A6-E
 ALL PARTITIONS REQUIRED TO HAVE FIRE RES
 ISTANCE RATING SHALL EXTEND FROM THE TOP
 OF THE FLOOR BELOW TO THE CEILING ABOVE
 AND SHALL BE SECURELY ATTACHED & SEALED,
 HAVING A FIRE RESISTANCE RATING AT LEAST
 EQUAL FOR THE PARTITION.
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412