2001-05-19 00:00:00REVIEW NOTES...FAILED..
  
 1) CHART FOR CSST PIPE NOT ACCEPTABLE.
 CHART 305.4F OF SGC-97 MUST BE USED. AND
 80' OF 1" CSST ONLY ALLOWS FOR 132,000
 BTU'S.
  
 2) 1/2" GALV. DROP TO RANGE TO BE SIZED
 AT 3/4". 1/2" ONLY ALLOWS FOR 57,000 BTU
 AT 80'.
  
 RESIZE AND RESUBMIT USING APPROIATE
 CHART AND PIPE.
  