Plan Review Notes For Permit 01050928 |
Permit Number |
01050928 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-05-18 00:00:00 | 1) THE FIRE ALARM AND FIRE SPRINKLER | | SYSTEMS ARE TO BE MONITORED BY A | | LICENSED UL LISTED CENTRAL STATION | | APPROVED BY THE FIRE RESCUE DEPARTMENT. | | 2) FIRE ALARM SYSTEM TO BE CLASS A OR | | FULLY ADDRESSABLE. | | 3) SMOKE DETECTORS WHEN INSTALLED ARE TO | | BE A MINIMUM OF THREE FEET FROM AIR | | CONDITIONER DIFFUSERS. | | 4) FIRE ALARM SYSTEM WHEN ACTIVATED IS | | TO BE AUDIBLE THROUGHOUT THE BUILDING. | | 5) FIRE ALARM HORN STROBE DEVICES ARE TO | | BE INSTALLED BETWEEN 80-96 INCHES FROM | | FINISHED FLOOR. | | 6) MANUAL PULL STATIONS SHALL BE MOUNTED | | BETWEEN 3 1/2 TO 4 1/2 FEET FROM THE | | FLOOR. | | | | CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|