Plan Review Notes
Plan Review Notes For Permit 01050928
Permit Number 01050928
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-05-18 00:00:001) THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS ARE TO BE MONITORED BY A
 LICENSED UL LISTED CENTRAL STATION
 APPROVED BY THE FIRE RESCUE DEPARTMENT.
 2) FIRE ALARM SYSTEM TO BE CLASS A OR
 FULLY ADDRESSABLE.
 3) SMOKE DETECTORS WHEN INSTALLED ARE TO
 BE A MINIMUM OF THREE FEET FROM AIR
 CONDITIONER DIFFUSERS.
 4) FIRE ALARM SYSTEM WHEN ACTIVATED IS
 TO BE AUDIBLE THROUGHOUT THE BUILDING.
 5) FIRE ALARM HORN STROBE DEVICES ARE TO
 BE INSTALLED BETWEEN 80-96 INCHES FROM
 FINISHED FLOOR.
 6) MANUAL PULL STATIONS SHALL BE MOUNTED
 BETWEEN 3 1/2 TO 4 1/2 FEET FROM THE
 FLOOR.
  