Plan Review Notes For Permit 01050883 |
Permit Number |
01050883 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2001-07-18 00:00:00 | ***************** UNSAT ************** | | | | 1)NOTE: PLEASE NOTE THAT ANY | | HANDWRITTENCHANGES ON PLANS ARE TO BE | | SIGNED,DATED BY ARCH OF RECORD. 481.221 | | | | 2)NOTE: PLEASE NOTE THAT LOAD | | CALCULATIONS DO NOT INCLUDE ALL LOADS | | REQ`D BY NEC ART 220. NO A/C, NO SM APPL | | PLEASE REVISE | | | | 3)NOTE: PLEASE NOTE THAT UTILITY ROOM | | OUTLET TO BE GFI PER 210-8. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELELCTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|