Plan Review Notes
Plan Review Notes For Permit 01050883
Permit Number 01050883
Review Stop E
Sequence Number 1
Notes
Date Text
2001-06-04 00:00:00***************** UNSAT **************
  
 1)NOTE: PLEASE NOTE THAT APPEARS THAT
 THE SERVICE IS BEING UPGRADED?
 PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2)NOTE: PLEASE NOTE THAT RISER DIAGRAM
 SHOWS PANEL AT 21POLE/CIRCUIT? PLEASE
 VERIFY THIS AS IT IS NOT A COMMON SIZE.
  
 3)NOTE: PLEASE VERIFY LOAD CALCUALTION\\
 FOR MAIN HOUSE LIGHTING. CALCS SHOW
 4725 WATTS, AND SQ FT ON PAGE 1 OF 5
 SHOWS SQ FT AT 1844, WHICH WOULD MAKE
 IT 5532? PLEASE CLARIFY.
  
 4)NOTE: PLEASESHOW LOCATION OF NEW
 PANEL.
  
 5)NOTE: PLEASE NOTE THAT A SMOKE
 DETECT--OR IS REQ`D OUTSIDE OF MASTER
 BEDROOM
 ALSO/ PER NFPA-72 2-2.1.1.1
  
  
 JUST A NOTE, PLEASE NOTE THAT IF THERE
 IS GOING TO BE ANY CATV AND OR
 TELEPHONE`S IN NEW ADDITION THEN THESE
 NEED TO BE SHOWN ON PLANS.
 PLEASE SHOW LOCATIONS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372