Plan Review Notes For Permit 01050883 |
Permit Number |
01050883 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-06-04 00:00:00 | ***************** UNSAT ************** | | | | 1)NOTE: PLEASE NOTE THAT APPEARS THAT | | THE SERVICE IS BEING UPGRADED? | | PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW EQUIPMENT BEING INSTALLED. | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | 2)NOTE: PLEASE NOTE THAT RISER DIAGRAM | | SHOWS PANEL AT 21POLE/CIRCUIT? PLEASE | | VERIFY THIS AS IT IS NOT A COMMON SIZE. | | | | 3)NOTE: PLEASE VERIFY LOAD CALCUALTION\\ | | FOR MAIN HOUSE LIGHTING. CALCS SHOW | | 4725 WATTS, AND SQ FT ON PAGE 1 OF 5 | | SHOWS SQ FT AT 1844, WHICH WOULD MAKE | | IT 5532? PLEASE CLARIFY. | | | | 4)NOTE: PLEASESHOW LOCATION OF NEW | | PANEL. | | | | 5)NOTE: PLEASE NOTE THAT A SMOKE | | DETECT--OR IS REQ`D OUTSIDE OF MASTER | | BEDROOM | | ALSO/ PER NFPA-72 2-2.1.1.1 | | | | | | JUST A NOTE, PLEASE NOTE THAT IF THERE | | IS GOING TO BE ANY CATV AND OR | | TELEPHONE`S IN NEW ADDITION THEN THESE | | NEED TO BE SHOWN ON PLANS. | | PLEASE SHOW LOCATIONS. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|