Plan Review Notes
Plan Review Notes For Permit 01050883
Permit Number 01050883
Review Stop B
Sequence Number 1
Notes
Date Text
2001-06-06 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01050883
 1329 10TH STREET
 O/B TAYLOR, MARLA/
 GREEN, SCOTTY
 820-0145
 ARTHER PATERSON
 842- 1944
 1)- SBC SSTD 10-97 FOR RESIDENTIAL
 BUILDINGS THAT ARE NOT DESIGNED BY A
 DESIGN PROFESSIONAL (ARCHITECT OR ENGINE
 ER) THE EQUIREMENTS ARE DEEMED TO SATIS-
 FY THE WIND LOAD PROVISIONS OF 1606 IN
 THE 1997 SBC SUBJECT TO THE LIMITATIONS
 IN GENERIC BUILDING GEOMETRY, SITING
 LOCATIONS, MATERIALS AND WIND CLIMATE
 SET FORTH WITHIN.
  
 2)- SSTD 10-97 303.1 MONOLITHIC SLAB
 CONFIGURATION, 20" TALL X 12" WIDE.
  
 3)- SSTD 10-97 TABLE 205 C IS GIVEN FOR
 THE SPACING OFVERTICAL STEEL AND THE
 BOND BEAM REQUIREMENTS.
  
 4)- SSTD 10-97: 205.8 GIVES THE O/B
 3 OPTIONS FOR TYPE OF BEAM.THE THREE
 CHOICES ARE OUTLINED ON PAGES 36/41
 THE MOST COMMONLY USED IN THIS AREA IS
 THE BEAM / LINTAL ASSEMBLY. PAGE 41
 INDICATES A 16" BEAM ALL CELLS ARE GROUT
 ED ABOVE THE LINTEL & THE AMOUNT OF
 STEEL REQUIRED FOR THE PLACEMENT IN THE
 LINTEL.
  
 5)- SBC 1606.2.6.2 COMPONENTS & CLADDING
 THERE IS NO DETAIL FOR THE ATTACHMENT OF
 WINDOW BUCKS TO THE BLOCK.
  
 6)- DISCREPANCIES: THE TRUSS PLAN SHOWS
 A DIFFERENT TRUSSED ROOF THAN THE ELEVAT
 IONS, THERE IS ALSO A 3'-0" INDINTATION
 IN THE EXTERIOR WALL WHICH THE TRUSS
 PLAN DOESN'T SHOW CREATING A 5'-0" OVER-
 HANG + VERY HIGH UPLIFT VALUES WHICH
 WILL NEED TO BE ADDRESSED.
  
 7)- THE PLAN DOESN'T INDICATE IF THE
 GABLE END IS TO BE WOOD FRAME OR BLOCK,
 IF THERE IS TO BE A DROPPED GABLE TO
 ALLOW FOR THE 2'-0" OVERHANG?
  
 8)- SBC 1606.4.1/1707.4.1 GLAZED OPENING
 WILL REQUIRE STORM SHUTTERS THAT MEET
 THE LARGE MISSLE IMPACT RESISTANCE TEST-
 ING, SBCCI REPORT OR DADE COUNTY ARE
 ACCEPTABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 EX 8412