2001-05-21 00:00:00****************UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT UNDER F.S./
 F.A.C. SERVICES CONTAINING 277/480
 NEED TO BE SIGNED AND SEALED BY A P.E.
 PLEASE ALSO NOTE THAT PLANS ARE SIGNED
 AND SEALED BUT SEAL IS CLEAR AND RAISED
 PER 471.025/481.221.
  
 2)NOTE: PLEASE NOTE THAT GROUNDING
 TRANSFORMERS IS SHOWN GOING TO CWP ON
 EACH FLOOR AT TRANSFORMER LOCATIONS.
 PLEASE NOTE THAT TRANSFORMER NEEDS TO
 BE ATTACHED EXSITING BLDG GROUNDING
 SYSTEM. IT IS NOT KNOW WHEATHER OR NOT
 IF THERE IS ANY PVC PIPE INBETWEEN
 UNDERGROUND WATER PIPE AND POINT OF
 CONNECTION AT TRANSFORMERS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  