2001-07-12 00:00:00 | SECOND CHECKLIST: |
| 1-STORM SHUTTERS INFORMATION STILL IS |
| INCOMPLETE. MISSING KEY PLAN AND |
| PROPER INSTALLATION SCHEDULE. |
| -PROVIDE COMPLETE INFORMATION OR APPLY |
| UNDER A SEPARATE PERMIT. |
| 2-PROVIDE NOTICE OF COMMENCEMENT. |
| 3-OWES $275.92 FOR LOW VALUATION. PLEASE |
| PAY ATTACHED RECEIPT. |
| 4-SEE PLANS FOR COMMENTS AND CORRECT AS |
| REQUIRED. PLEASE RETURN REVIEWED SET |
| AFTER CORRECTIONS ARE DONE IN ORDER TO |
| EXPEDITE THE REVIEW PROCESS. |
| 5-PROVIDE PRODUCT APPROVAL FOR: |
| A)DOUBLE ENTRY DOORS AS SHOWN ON PLANS. |
| B)FRENCH DOORS WITH SIDELITES & TRANSOM |
| ABOVE SINGLE ASSEMBLY AS SHOWN ON |
| PLANS. |
| C)FRENCH DOORS W/ TRANSOM ABOVE SINGLE |
| ASSEMBLY AS SHOWN ON PLANS. |
| D)MULLIONS FOR HORIZONTAL ASSEMBLIES. |
| PRODUCT APPROVAL SUBMITTED IS FOR |
| VERTICAL APPLICATIONS ONLY. |
| E)GARAGE "OUTSWING" SIDE DOORS. PRODUCT |
| APPROVAL SUBMITTED IS FOR "INSWING". |
| |
| NOTE: PRODUCT APPROVAL PACKAGE SUBMITTED |
| IS THE SAME THAT WAS SUBMITTED BEFORE. |
| COMMENTS FROM MY PREVIOUS CHECKLIST WERE |
| NOT ADDRESSED. |
| |
| 6-UPDATE: |
| A)RINKER LETTER FOR MASONRY UNITS. |
| B)ENGINEERING SPECS FOR PRECAST LINTELS |
| SIGNED, SEALED AND DATED AS REQUIRED |
| BY CHAPTER 471 OF FLORIDA STATUTES. |