Plan Review Notes For Permit 01050665 |
Permit Number |
01050665 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-06-04 00:00:00 | *******************DENIED*************** | | | | PLEASE PROVIDE OUTSIDE AIR CALCULATIONS | | AS PER ASHRAE 62-89. | | | | NO COMBUSTIBLES ABOVE CEILING IN RETURN | | AIR PLENUM (1997 SMC 609.1.1). | | | | FIRE DAMPERS SHALL COMPLY WITH UL 555 | | AND SHALL BEAR LABLE OF APPROVED | | TESTING AGENCY (1997 SMC 610.1.1). | | | | NOTE:PRIOR TO CONNECTING TO ANY | | EXISTING DUCTWORK, CALL FOR AN | | INSPECTION. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|