Review Stop M
Sequence Number 1
Notes
Date Text
2001-05-17 00:00:00*******************PROVISO**************
  
 APPROVED 12/26/00 ON MASTER PERMIT #0004
 0884 WITH THE FOLLOWING PROVISO.
  
 1.RE: NOTE ON SHAFT REMOVAL ORTO
 MODIFICATION, 1997 SMC 610.4 -
 DUCTS EXTENDING THROUGH MORE THAN
 ONE FLOOR TO BE PROTECTED BY SHAFT
 ENCLOSURE HAVING A FIRE RESISTANCE
 NOT LESS THAN 2 HRS FOR A BUILDING
 4 STORIES AND MORE IN HEIGHT.PLAN
 UNCLEAR AS TO WHAT WILL BE CHANGED.
 THIS CODE SHALL BE COMPLIED WITH
 FOR ANY CHANGES.
  
 2.LOCAL AMENDMENT 304.2.5 REQUIRES A
 MINIMUM 18" CLEARENCE BETWEEN ROOF
 SURFACE AND BOTTOM OF SUPPORT
 STRUCTURE OF STAND.PLAN INDICATES
 EXPIRED DADE CO. APPROVAL.
  
 3.NOTE 5 AND 6 SHOW OUTSIDE AIR AND
 EXHAUST AIR NEXT TO EACH OTHER.
 CODE REQUIRES A 10 FT SEPARATION
 BETWEEN THE TWO. (1997 SMC 506.1)
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096EXT. 8388.