2001-06-04 00:00:00*******************DENIED***************
  
 PLEASE PROVIDE OUTSIDE AIR CALCULATIONS
 AS PER ASHRAE 62-89.
  
 CONDENSATE SHALL NOT GO TO SANITARY
 WASTE.UNITS 3 TON AND LARGER SHALL GO
 TO EITHER STORM DRAIN OR APPROVED DRY
 WELL.
  
 IF CEILING IS USED AS RETURN AIR
 PLENUM, NO COMBUSTILBLES SHALL BE IN
 THIS SPACE (1997 609.1.1).
  
 FAN SHUTDOWN BY DUCT SMOKE DETECTOR AS
 PER 1997 SMC 406.1, WITH NOTIFICATION
 TO ALARM/STROBE IN NORMALLY OCCUPIED
 AREAS AS PER NFPA 90A 4-4.4.3.
  
 PLEASE PROVIDE INFORMATION AS TO WHAT IS
 BEING STORED IN THE "POOL STORAGE" AREA
 AND IS THERE ANY MEANS OF VENTILATION?
  
 NOTE:SHOULD THE WALK-IN COOLER BE A
 PART OF THE RENOVATION/ADDITION,
 AN ADDITIONAL MECHANICAL PERMIT
 AND PLANS WILL BE REQUIRED.
  