Plan Review Notes For Permit 01050516 |
Permit Number |
01050516 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-06-05 00:00:00 | THE MIAMI DADE PRODUCT ACCEPTANCE # | | 99-0716.03 (ROOF TILES) EXPIRED 1/22/01 | | | | THE "FLORIDA QUALITY TRUSS" LAYOUT CITES | | 110 MPH.WEST PALM BEACH IVOKES ASCE | | 7-95 THROUGH THE SBC, WHICH PLACES THE | | CITY IN AN 145 MPH ZONE. REVISE AS | | NECESSARY. | | | | SHOW THE DESIGN LOADS FOR THE FLOOR | | TRUSSES.SEE SBC 1603 & 1604. | | | | WILL THE FLOOR TRUSSES BE TOP CHORD | | BEARING ON THE 2 X 6 LEDGER SUPPORTED | | BY 1/4" TAPCONS 2' O.C.?IF SO PROVIDE | | A STRESS ANALYSIS.SEE SBC 104.2 | | | | THE HC RAMP REQUIRES HANDRAILS ON EACH | | SIDE.EDGE PROTECTION.SEE 4.8 OF THE | | FACBC | | | | SHOW THE SAFETY GLAZING IN TH AREA OF | | THE DOOR IN ACCORDANCE WITH SBC | | 2405.2.1. | | | | THE DRESSING ROOM IS REQUIRED TO BE HC | | ACCESSIBLE.SEE 4.35 OF THE FACBC | | | | THE OFFICE IS REQUIRED TO BE ON AN | | ACCESSIBLE ROUTE.SEE 4.1.6 (B) FACBC | | | | A PORTION OF THE COUNTER IS REQUIRED TO | | BE ACCESSIBLE. SEE 7.2 (1) FACBC |
|