Plan Review Notes
Plan Review Notes For Permit 01050329
Permit Number 01050329
Review Stop P
Sequence Number 2
Notes
Date Text
2001-06-11 00:00:00REVIEW NOTES: FAILED
  
 1) INDICATE NATURAL OR L/P GAS.
  
 2) PSI INDICATED IS 20 PSI. IF THIS IS
 A 2 PSI SYSTEM, REGULATORS ARE NOT SHOWN
 FOR SECOND STAGE PRESSURE.
  
 3) COPY OF APPROIATE GAS SIZING TABLES
 ARE REQUIRED.
  
 4) PLEASE INDICATE WHICH MODEL FIREPLACE
 AND SHOW WHERE THE BTU RATING IS LOCATED
  
 5) INDICATE IN WHICH ROOM THE FIREPLACE
 WILL BE LOCATED, AND GIVE COMBUSTION AND
 VENTILATION AIR CALCULATIONS FOR ROOM AS
 SHOWN ON PAGE 3 OF THE INSTALLATION
 INSTRUCTIONS.
  
 6) RE: 1/2 SHEET FURNISHED WITH FIRE-
 PLACE. PLEASE SUBMIT ALL INFORMATION
 FROM THAT SHEET.
  
 7) BTU'S FOR GAS GRILL INDICATE ON RISER
 DIAGRAM 60,000 BTU'S, BUT ONLY 40,000 IN
 INSTRUCTION MANUAL. PLEASE CLARIFY.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377