2001-06-06 00:00:00 | *************BUILDING UNSAT************* |
| |
| 1)PROVIDE (2) CURRENT AND COMPLETE |
| COPIES OF SBCCI OR METRO-DADE PRODUCT |
| APPROVALS FOR: |
| - EXTERIOR WINDOWS |
| - EXTERIOR DOORS |
| - GARAGE DOOR |
| - STORM PANELS |
| - GLASS BLOCK |
| |
| 2) PROVIDE (2) PRODUCT APPROVALS, KEY |
| PLANS AND INSTALLATION SCHEDULES |
| INDICATING THE SPECIFIC TYPES OF ANCHORS |
| TO BE USED FOR STORM PANELS. |
| |
| 3) PROVIDE SOIL TEST PER SEC. 1804.2.2 |
| OF CITY AMENDMENTS TO 1997 SBC. |
| |
| 4) PROVIDE ENERGY CALCULATIONS AND |
| MANUAL "J" CALCULATIONS PER 97 FLORIDA |
| ENERGY CODE FOR BUILDING CONSTRUCTION. |
| |
| 5) WALL SECTIONS 4&5 ON A-6 INDICATE |
| R-13 INSULATION AND THE FLOOR PLAN ON |
| A-2 INDICATES R-11 INSULATION PLEASE |
| CORRECT. |
| |
| 6) THE SCALES GIVEN FOR THE ELEVATIONS |
| ON A-3 ARE INCORRECTLY LISTED AS 1/8" = |
| 1'-0". PLEASE CORRECT. |
| |
| 7) PROVIDE CONSTRUCTION DETAILS FOR ARCH |
| OPENINGS IN EXTERIOR WALLS. |
| |
| 8) PROVIDE DESIGN COMPLIANCE FORM TO |
| INDICATE THE DESIGN PARAMETERS AND |
| ASSUMPTIONS USED FOR THIS STRUCTURE. |
| |
| 9) SPACING OF VERTICLE WALL REINFORCE- |
| MENT DOES NOT COMPLY WITH SSTD 10-97. |
| PEASE REVIEW AND CORRECT, IF USING THE |
| PRESCRIPTIVE METHOD OF DESIGN COMPLIANCE |
| |
| 10) PROVIDE DESIGN PARAMETERS AND |
| ASSUMPTIONS USED TO DETERMINE FORCES AND |
| REACTIONS APPLIED TO ROOF TRUSSES AND |
| GIRDERS. |
| |
| 11) INDICATE THE TRUSS CONNECTORS THAT |
| WILL BE USED ON THE TRUSSES THAT ARE NOT |
| SPECIFICALLY INDICATED ON PLANS. |
| |
| 12) INDICATE MEAN ROOF HEIGHT ON PLANS. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)659-8096 EXT.8202 |