Plan Review Notes
Plan Review Notes For Permit 01041386
Permit Number 01041386
Review Stop E
Sequence Number 1
Notes
Date Text
2001-05-07 00:00:00***************** UNSAT **************
  
 1)NOTE: PLEASE NOTE THAT WIRING DIAGRAM
 ON PLANS DO NOT SHOW HEAT PUMP OR ASSC
 WIRING? PLEASE INCLUDE ON WIRING DIAGRAM
 WIRING ETC.
  
 2)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 FOR ADDED LOAD ON EXISTING SERVICE.
 PLEASE SHOW SIZE OF EXISTING SERVICE
 WITH ALL NEW LOADS ADDED.
 215-5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096