2001-05-08 00:00:00 | PLAN REVIEW: 01041205 |
| 1400 NORTHPOINT PARKWAY |
| SUITE # 10 |
| BUTTERS CONSTRUCTION |
| PHONE 954/570-8111 EX.34 |
| FAX954/570-8844 |
| |
| INCLUDED IS A COPY OF THE PROSIVO FOR |
| THE TENANT BUILDOUT. IN THIS PROVISO |
| THE ADDITIONAL INFORMATION REQUIRED |
| FOR THE REMAINDER OF THE TENANT BUILDOUT |
| WAS TO BE PROVIDED. |
| THE PERMIT AND REQUIRED INFORMATION FOR |
| THE DECK AS WELL AS THE 500 GAL NITROGEN |
| TANK. |
| |
| THE ITEMS LISTED BELOW ARE THE SAME |
| ITEMS THAT WERE LISTED ON THE REVIEW OF |
| 4/27/01 (BROUGHT IN AS A REVISION). |
| |
| 1)- HOW WILL THE TANK BE FASTENED TO THE |
| SLAB TO RESIST OVERTURNING IN A CASE OF |
| A HURRICANE? IS THERE A SAFETY FACTOR |
| FIGURED IN TO THE FORMULA? |
| |
| 2)- THE AREA NEXT TO THE NITROGEN TANK |
| IS TO BE USED FOR A LOUNGE AREA, WHAT |
| SAFETY FEATURES ARE TO BE CONSIDERED FOR |
| GAS LEAKS, THE CONCERN IS SIMPLE |
| ASPHYXIATION. |
| |
| 3)- THE INTERIOR BUILD OUT HAD THE 2 |
| DOORS LEADING INTO THE SCREEN ENCLOSURE |
| AS EXIT DOORS, SHOW PATH OF TRAVEL, AND |
| OCCUPANT LOAD TAKEN BY THE REMAINING |
| DOORS. |
| |
| 4)- ITEM #5 OF THE PROVISO: THE |
| ARCHITECT WILL CORRECT THE FLOOR DRAIN |
| SHOWN IN THE ISOMETRIC FOR THE CONTAIN- |
| MENT ROOM, NOT CORRECTED AS OF PLANS SUB |
| MITTED. |
| |
| BUILDING PLAN REVIEW |
| JIM WITMER |
| (561) 659-8096 EX 8412 |