2001-05-08 00:00:00PLAN REVIEW: 01041205
 1400 NORTHPOINT PARKWAY
 SUITE # 10
 BUTTERS CONSTRUCTION
 PHONE 954/570-8111 EX.34
 FAX954/570-8844
  
 INCLUDED IS A COPY OF THE PROSIVO FOR
 THE TENANT BUILDOUT. IN THIS PROVISO
 THE ADDITIONAL INFORMATION REQUIRED
 FOR THE REMAINDER OF THE TENANT BUILDOUT
 WAS TO BE PROVIDED.
 THE PERMIT AND REQUIRED INFORMATION FOR
 THE DECK AS WELL AS THE 500 GAL NITROGEN
 TANK.
  
 THE ITEMS LISTED BELOW ARE THE SAME
 ITEMS THAT WERE LISTED ON THE REVIEW OF
 4/27/01 (BROUGHT IN AS A REVISION).
  
 1)- HOW WILL THE TANK BE FASTENED TO THE
 SLAB TO RESIST OVERTURNING IN A CASE OF
 A HURRICANE? IS THERE A SAFETY FACTOR
 FIGURED IN TO THE FORMULA?
  
 2)- THE AREA NEXT TO THE NITROGEN TANK
 IS TO BE USED FOR A LOUNGE AREA, WHAT
 SAFETY FEATURES ARE TO BE CONSIDERED FOR
 GAS LEAKS, THE CONCERN IS SIMPLE
 ASPHYXIATION.
  
 3)- THE INTERIOR BUILD OUT HAD THE 2
 DOORS LEADING INTO THE SCREEN ENCLOSURE
 AS EXIT DOORS, SHOW PATH OF TRAVEL, AND
 OCCUPANT LOAD TAKEN BY THE REMAINING
 DOORS.
  
 4)- ITEM #5 OF THE PROVISO: THE
 ARCHITECT WILL CORRECT THE FLOOR DRAIN
 SHOWN IN THE ISOMETRIC FOR THE CONTAIN-
 MENT ROOM, NOT CORRECTED AS OF PLANS SUB
 MITTED.
  